Pressure, differential pressure and temperature

A reliable reading depends on the complete assembly: process tapping or thermowell, transmitter and a correctly configured control-system input.

The whole application matters.

Engineering combines operating conditions, material compatibility and maintenance access. A sensor may require a valve manifold, diaphragm seal or thermowell. These accessories influence mechanical integrity, response and measurement uncertainty, so they belong in the same specification.

Scope of the solution

  • Sensor and assembly specification
  • Process and electrical connections
  • Calibration and signal checks
  • Thermowell manufacture using gun drilling / deep-hole drilling to approved drawings, with agreed dimensional inspection.
  • Pressure-instrument and temperature-sensor calibration using our own hydraulic pressure calibrator and temperature calibrator.

From operating need to design.

01

Pressure taps and manifolds

Gauge, absolute and differential pressure are different quantities. Differential measurement also requires consideration of static pressure and both connection paths. The connecting assembly must suit the required function and the process medium.

02

Temperature in pipes and vessels

An RTD or thermocouple needs an appropriate range, construction and immersion length. A thermowell requires assessment of flow and mechanical loading, beyond simply matching the connection and material grade.

03

Reactor temperature profiles

Multipoint measurement can reveal temperature distribution. The specification defines point locations, supports, sensor routes and junction-box or transmitter interfaces. The number of points follows from process requirements and the vessel construction.

04

Thermowells manufactured in-house

We use our own gun-drilling equipment to produce deep bores in thermowells. Engineering documents define the material, process connection, insertion length, bore diameter and depth, and sensor fit. Fabrication and dimensional inspection follow the approved drawing and the requirements of the specific measuring assembly.

05

Our own pressure and temperature calibrators

Our hydraulic pressure calibrator and temperature calibrator support inspection and calibration of the corresponding instruments and sensors. The range, connections and calibration points are defined for the instrument. Transmitter settings and outputs can also be checked as specified, relating results to the actual measuring-assembly configuration.

Inputs that matter.

  • Medium, range and abnormal conditions.
  • Pressure, temperature, flow and vibration.
  • Connections, immersion and available space.
  • Response, accuracy and control interface.
  • Environment and required documentation.
Prepare your brief →

Outputs and acceptance.

  • Complete assembly datasheets.
  • Installation drawings and accessory list.
  • Inspection plan and configuration records.

The actual scope and acceptance criteria depend on the application and contract.

Pressure: measurement reference and process connection

Define the pressure reference and measuring range first; a diaphragm seal is a process connection arrangement, not an additional pressure reference.

On a small screen, scroll the table sideways to compare the selection criteria.

Pressure: measurement reference and process connection
Principle or optionTypical applicationWhat to verify when selecting
Gauge pressureProcess pressure relative to ambient atmosphere, for example at a pump or utility header.Whether the required value is gauge or absolute; also overload, pressure surges, range and reference venting conditions.[1]
Absolute pressurePressure referenced to vacuum for vacuum processes or calculations requiring absolute pressure.Required vacuum and positive-pressure range, uncertainty at the operating point and sensor compatibility with the fluid.[1]
Differential pressureFilter pressure loss, flow across a primary element, or level in a closed tank.Differential range and static pressure, one-sided overload, tap positions and connecting-line arrangement.[1][2]
Diaphragm seal, with capillary where requiredSeparation of a gauge or transmitter from the fluid under demanding material, hygienic or temperature conditions.Diaphragm and fill fluid, process and ambient temperature, capillary length and elevation, and assembly effects on response and error.[3]
Sources for this comparison
  1. WIKA – Introduction to differential pressure measurement ↗
  2. Endress+Hauser – Differential pressure flow measurement ↗
  3. WIKA – Capillary tubes in pressure measurement ↗

Reviewed on 18 October 2026. Selection is confirmed for the specific operating conditions and equipment design.

Comparing temperature measurement options

Beyond range and accuracy, consider measurement location, process dynamics and thermal contact, because surface temperature may differ from the fluid temperature inside equipment.

On a small screen, scroll the table sideways to compare the selection criteria.

Comparing temperature measurement options
Principle or optionTypical applicationWhat to verify when selecting
Resistance temperature detector, RTDContact process temperature measurement where stability and repeatability matter.Sensor type and wiring arrangement, lead resistance, immersion, thermowell and complete assembly response.[1][2]
ThermocoupleContact measurement in demanding thermal processes; suitability depends on thermocouple type and protective construction.Metal pair, environment, polarity, extension or compensating cable, and cold-junction compensation.[1][2]
Bimetal thermometerLocal dial indication for operators without an electrical power supply.Range, active stem length and immersion, mounting orientation, readability and installation vibration.[3]
Infrared measurementNon-contact surface temperature measurement of moving, hot or difficult-to-access objects.Emissivity and reflections, target size, distance, optical path and a spectral range appropriate to the material.[4]
Sources for this comparison
  1. WIKA – Temperature measurement overview ↗
  2. WIKA – Temperature transmitter T32, technical data TE 32.04 ↗
  3. WIKA – Bimetal thermometers: selection and application ↗
  4. Optris – Non-contact temperature measurement FAQs ↗

Reviewed on 18 October 2026. Selection is confirmed for the specific operating conditions and equipment design.

Expertise for this application.

Connect the whole solution.

Questions that shape the project.

Is a diaphragm seal always beneficial?

It protects the instrument in particular applications, but the complete assembly needs assessment. Fill fluid, capillary and ambient temperature can affect both response and measurement error.

Is the catalogue temperature range enough?

It is one input. Materials, temperature cycles, immersion length, mechanical loading and required response time also determine whether the assembly is suitable.

A clear brief.